AutomaticDigital Humidifier ControlModel 60 &62Safety and Installation InstructionsWARNINGATTENTION INSTALLER: This product must beinstalled by a
1918Blower Activation Test• Deactivate HVAC system or heat pump.• Turn knob to OFF.• Set switch to Blower Activation ON.• Turn the knob to Test/Reset.
2120TROUBLESHOOTING GUIDESYMPTOMCall Dealer For Service Light Flashing (see Figure M).TROUBLESHOOTING PROCEDUREApplies to both Automatic and Manual Op
2322TABLE 1Outdoor Temperature (°F) Resistance (kΩ) ±10-30 231.8-20 163.4-10 117.30 84.810 62.220 46.130 34.440 26.150 19.960 15.370 11.980 9.390 7.31
2524SYMPTOMYellow “Change Water Panel” light is blinking (see Figure M).TROUBLESHOOTING PROCEDURECheck the condition of the Water Panel and replace it
2726SYMPTOMHumidifier operates constantly.• If the humidity level in the home is less than the HumidifierControl knob setting and there is a continuou
28RESEARCH PRODUCTS CORPORATIONP.O. BOX 1467 • MADISON,WI 53701-1467Call 800/334-6011 • FAX 608/257-435710008977 6.10B2205119A
32Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 4System Checkout . . . . . . . . . . . . . . . . . .
54STEP 2: Disassemble the Humidifier ControlRemove the knob. Remove the cover by pulling at the bottom andswinging it out and upward.STEP 3: Check the
76STEP 4: Determine Location for Humidifier Controland Mount ControlHumidifier Control must be mounted on the Return Duct, at least6 inches upstream o
98Figure D – Fiber Board Duct Mount90-1203BCONTROL BOARDCOVERKNOBBASE PLATERETURN DUCTRETURNDUCTSHEET METALPLATECUT OPENING INRETURN DUCTSHEET METAL P
1110STEP 7: Alternate Location for OutdoorTemperature SensorThe Sensor can also be mounted in the center of either:• PVC fresh air intake pipe for the
1312Installing the Humidifier Control forManual OperationIf it is not feasible to install the Outdoor TemperatureSensor, the Humidifier Control can be
GYWCRTHERMOSTAT120 VACRCWYGFURNACEOUTDOORTEMPERATURESENSOR FORAUTOMATICMODENORTH, EASTOR WEST SIDEOF HOMEABOVE EXPECTEDSNOW LINECONTINUOUSLY POWERED24
1716OUTPUTSINPUTSPOWERGWCRHHODT GfAADHC TERMINAL STRIPBMODEL 800STEAM HUMIDIFIEROUTDOOR TEMPERATURE SENSORFOR AUTOMATIC MODEFURNACETHERMOSTATRCWYGGYWC