Model 76 Dehumidifier ControlInstallation InstructionsREAD AND SAVE THESE INSTRUCTIONS CAUTION1. Read all instructions before beginning installation.
TABLE 3 – Troubleshooting GuideSymptom Possible Reason Troubleshooting ProcedureNo power to the control.Incorrect wiring. Verify wiring connections be
P.O.Box1467•Madison,WI53701-1467•Phone:800/334-6011 •Fax:608/257-4357www.aprilairepartners.com10009850 2.12B2205738APrinted in U.S.A.© 20
TABLE OF CONTENTSSafety Instructions... 1Overview ... 3Specifications... 3Location Recommenda
LOCATION RECOMMENDATIONSMOUNT CONTROL•Inanareathehomeownerwantstomonitor and control moisture levels.•Onaninteriorwall.•Approximately
REQUIRED COMPONENTS18 – 24 gauge wire (field supplied) – 4 wires required, run new cable as needed. (2)#8x1-1/2”mountingscrews(supplied) (2) Anc
WIRINGSTEP 2 – SUPPLY 24VAC TO THE MODEL 76 CONTROLThe Model 76 control requires 24VAC when installed as an EXTERNAL CONTROL for the 1730A. Pulling po
MODEL 76 REMOTE CONTROL TO 1710A /1750A /1770A1. Disconnect power to the dehumidifier and HVAC system.2. Remove the control door on the dehumidifier
FIGURE 13 – Remote Control90-1636Model 76 ControlModel 76 LCD DisplaySolid ON: Control On Blinking ON: DehumidifyingMeasured Humidity in Remote Loca
SEQUENCE OF OPERATIONEXTERNAL CONTROLNormal Mode•Whenthemeasuredhumidityisgreaterthanthesetting,thecontrolwillactivatethedehumidifier
TABLE 2 – Error CodesModel 76 Error CodeFailure Mode Fault Type Failure Condition ActionE1 Internal dehumidifier RH sensor fault.Critical RH sensor no